When combined with the Ultra 4 Controller, the dB3 with double sun shields has achieved MCERTS Class 1 Certification with 0.136% combined accuracy. This means that the pair have been independently tested and performed well under rigorous conditions. Utilities across the globe can now be confident that their flow measurement is of the highest possible accuracy by using MCERTS certified equipment.
The dB3 with double sun shields is specifically designed for open channel flow applications. One of the critical conditions of ultrasonic measurement is the measurement distance, therefore, its short measurement range of 3 m (9ft) and maximized accuracy at zero blanking meet this requirement. The double sun shields of the dB3 help to protect the transducer from solar radiation and combats ambient temperature changes that could ultimately affect the flow and level readings.
To achieve the MCERTS Class 1 Certification, the dB3 with double sun shields must be combined with the Ultra 4 controller from Pulsar Measurement. If you’d like to discuss your application requirements, please don’t hesitate to contact one of our friendly team who will be happy to help.
- MCERTS Class 1 Certification when combined with the Ultra 4
- Short measurement range, increases accuracy
- Protection from solar radiation
- Zero blanking distance
| General Specifications | |
|---|---|
| Spec: | Description: |
| Sensor Body Dimensions: | 180 mm D (sunshield) x 115 mm H (7.08 in x 4.5 in) |
| Weight: | Nominal 1.1 kg (2.4 lb) |
Max. and Min Temperature (Electronics): | Standard: -40 °C to +90 °C (-40 °F to +194 °F) ATEX: -40 °C to +75 °C (-40 °F to +167 °F) |
Measurement Range: | 125 mm to 3 m (4.9 in to 9.8 ft) |
| Accuracy: | 0.25% or 6 mm (0.2 in) whichever is greater |
Resolution: | 0.01% or 2 mm (0.08 in) whichever is greater |
Sensor Body Material: | Valox 357 U and syntactic foam face |
Maximum Separation: | 500 m (1,640 ft) |
Mounting Connection: | BSP or 1” NPT |
ENVIRONMENTAL | |
Enclosure Protection: | IP68 / NEMA 6P |
APPROVALS | |
CE Approval: | 2014/30/EU - EMC & 2014/34/EU ATEX Directives. Standards applied: EN 60079-0:2012+A11:2013/ EN 60079-11:2012 / EN 60079-18:2009 / EN 60079-26:2007 / EN 61326-1:2013 |
ATEX Approval: | Standard ATEX EEx m II T6 or optional EEx ia IIC T6. FM/FMC approval. |
MCERTs Certification: | Class 1 (0.136%) when used with Ultra 4 |
PERFORMANCE | |
Frequency: | 125kHz |
Beam Angle: | <10° |
| Fiche de données | Télécharger |
| MCERTS Certification | Télécharger |
| Case Study | Techno Bangla Engineering Ltd provides a non-contacting flow measurement solution to the pharmaceutical industry. | Télécharger |
| Pulsar Measurement Product Warranty | Télécharger |
- CE Approval: 2014/30/EU - EMC & 2014/34/EU ATEX Directives.
- CE Standards Applied: EN 60079-0:2012+A11:2013
- EN 60079-11:2012
- EN 60079-18:2009
- EN 60079-26:2007
- EN 61326-1:2013
- ATEX: Standard ATEX EEx m II T6 or optional EEx ia IIC T6.
- FM/FMC Approval
- MCERTS Class 1 Certification (when combined with the Ultra 4)
Demander un devis
Formulaire rapide
Configurateur de produit
Le configurateur de produits Pulsar Measurement vous permet de sélectionner les applications qui vous sont spécifiques et de découvrir les solutions les plus adaptées à vos besoins.